30 C.F.R. § 18.24

Electrical clearances

Read at: eCFRecfr.gov CornellLII GovInfogovinfo.gov CasesGoogle Scholar

Minimum clearances between uninsulated electrical conductor surfaces, or between uninsulated conductor surfaces and grounded metal surfaces, within the enclosure shall be as follows:

Minimum Clearances Between Uninsulated Surfaces

Phase-to-Phase Voltage (rms)Clearances (inches)
Phase-to-PhasePhase-to-Ground or Control Circuit
0 to 2500.250.25
251 to 6000.280.25
601 to 10000.610.25
1001 to 24001.40.6
2401 to 41603.01.4
[57 FR 61209, Dec. 23, 1992]