46 C.F.R. § 154.906 (2026)
Inert gas generators
Edition and currency
Other sources
The inert gas generator must:
(a) Produce an inert gas containing less than 5% oxygen by volume;
(b) Have a device to continuously sample the discharge of the generator for oxygen content; and
(c) Have an audible and visual alarm in the cargo control station that alarms when the inert gas contains 5% or more oxygen by volume.