46 C.F.R. § 28.330 (2026)
Galley hood and other fire protection equipment
Edition and currency
Other sources
(a) Each vessel must be fitted with a grease extraction hood complying with UL 710 above each grill, broiler, and deep fat fryer.
(b) Each grease extraction hood must be equipped with a pre-engineered dry or wet chemical fire extinguishing system meeting the applicable sections of NFPA 17 or 17A and must be listed by an independent laboratory.
(c) A vessel 79 feet (24 meters) or more in length must have at least one fire axe located in or adjacent to the operating station.