External loads
(a) Anticipated external loads (e.g., earthquakes, vibration, thermal expansion, and contraction) must be provided for in a pipeline system's design. Sections 401, 402, 403.3, and 403.9 of ASME B31.4 (incorporated by reference, see § 195.3) must be followed to provide for expansion and flexibility.
(b) The pipe and other components must be supported in such a way that the support does not cause excess localized stresses. In designing attachments to pipe, the added stress to the wall of the pipe must be computed and compensated for.
Syfert holds no separate history line for this section. Where this code prints a source or history note, it appears with the text, usually at the end.
Edition shown: eCFR text as of Sept. 29, 2026. Syfert holds no earlier or later version of this section.