Abandonment or deactivation of facilities

Edition and currency
eCFR text as of Sept. 29, 2026. The text is the edition Syfert holds; for a past event, check the version in force on that date.
Other sources
CURRENTeCFR text as of Sept. 29, 2026 cited 2004–2016 3citing cases
At a glance

Courts have cited this section in 3 opinions since 2004. The most litigated part is subsection (d) (1 case).

(a) Each operator shall conduct abandonment or deactivation of pipelines in accordance with the requirements of this section.

(b) Each pipeline abandoned in place must be disconnected from all sources and supplies of gas; purged of gas; in the case of offshore pipelines, filled with water or inert materials; and sealed at the ends. However, the pipeline need not be purged when the volume of gas is so small that there is no potential hazard.

(c) Except for service lines, each inactive pipeline that is not being maintained under this part must be disconnected from all sources and supplies of gas; purged of gas; in the case of offshore pipelines, filled with water or inert materials; and sealed at the ends. However, the pipeline need not be purged when the volume of gas is so small that there is no potential hazard.

(d) Whenever service to a customer is discontinued, one of the following must be complied with:

(1) The valve that is closed to prevent the flow of gas to the customer must be provided with a locking device or other means designed to prevent the opening of the valve by persons other than those authorized by the operator.

(2) A mechanical device or fitting that will prevent the flow of gas must be installed in the service line or in the meter assembly.

(3) The customer's piping must be physically disconnected from the gas supply and the open pipe ends sealed.

(e) If air is used for purging, the operator shall insure that a combustible mixture is not present after purging.

(f) Each abandoned vault must be filled with a suitable compacted material.

(g) For each abandoned offshore pipeline facility or each abandoned onshore pipeline facility that crosses over, under or through a commercially navigable waterway, the last operator of that facility must file a report upon abandonment of that facility.

(1) The preferred method to submit data on pipeline facilities abandoned after October 10, 2000, is to the National Pipeline Mapping System (NPMS) in accordance with the NPMS “Standards for Pipeline and Liquefied Natural Gas Operator Submissions.” To obtain a copy of the NPMS Standards, please refer to the NPMS homepage at www.npms.phmsa.dot.gov. A digital data format is preferred, but hard copy submissions are acceptable if they comply with the NPMS Standards. In addition to the NPMS-required attributes, operators must submit the date of abandonment, diameter, method of abandonment, and certification that, to the best of the operator's knowledge, all of the reasonably available information requested was provided and, to the best of the operator's knowledge, the abandonment was completed in accordance with applicable laws. Refer to the NPMS Standards for details in preparing your data for submission. The NPMS Standards also include details of how to submit data. Alternatively, operators may submit reports by mail to the Office of Pipeline Safety, Pipeline and Hazardous Materials Safety Administration, U.S. Department of Transportation, Information Resources Manager, PHP-10, 1200 New Jersey Avenue SE, Washington, DC 20590-0001 or by email to [email protected]. The information in the report must contain all reasonably available information related to the facility, including information in the possession of a third party. The report must contain the location, size, date, method of abandonment, and a certification that the facility has been abandoned in accordance with all applicable laws.

(2) [Reserved]

[Amdt. 192-8, 37 FR 20695, Oct. 3, 1972, as amended by Amdt. 192-27, 41 FR 34607, Aug. 16, 1976; Amdt. 192-71, 59 FR 6585, Feb. 11, 1994; Amdt. 192-89, 65 FR 54443, Sept. 8, 2000; 65 FR 57861, Sept. 26, 2000; 70 FR 11139, Mar. 8, 2005; Amdt. 192-103, 72 FR 4656, Feb. 1, 2007; 73 FR 16570, Mar. 28, 2008; 74 FR 2894, Jan. 16, 2009; Amdt. 192-135, 89 FR 33282, Apr. 29, 2024; Amdt. 192-172, 91 FR 21978, Apr. 24, 2026]
The 3 cases that cite 49 C.F.R. § 192.727 most heavily, weighted by court and treatment. RelevanceNewestTreatment
1
GREENJones v. Centerpoint Energy Entex, 66 So. 3d 539 (La. Ct. App. 2011).
cites § 192.727 6×subsections: (d) 2× (d)(1) (d)(2) (d)(3)cited by 9 cases
Where it cites § 192.727
“It was not disputed at trial that Center-point Energy’s applicable standard of care in disconnecting service to a customer is governed by 49 C.F.R. 192.727, which provides three methods of acceptable compliance: Whenever service to a customer is discontinued, one of the…”
2
GREENKevin Westbrook v. Atlanta Gas Light Co., 796 S.E.2d 320 (Ga. Ct. App. 2016).
cites § 192.727 2×cited by 1 case
Where it cites § 192.727
“3 Regardless of whether AGL’s characterization of the applicable federal 3 The plaintiffs cite 49 CFR § 192.727 (d), which requires that: Whenever service to a customer is discontinued, one of the following must be complied with: (1) The valve that is closed to prevent the flow…”
3
GREENS. Union Co. v. Lynch, 321 F. Supp. 2d 328 (D.R.I. 2004).
cites § 192.727 1×cited by 4 cases
Where it cites § 192.727
“379 (c) (providing that “[t]he customer’s piping must be physically disconnected from the gas supply and the open pipe ends sealed” under circumstances when a service line is not placed in operation); 49 C.F.R. § 192.727 (d)(3) (requiring that the “customer’s piping must be…”

The flag is Syfertize’s treatment of the citing case itself, not of the statute. “Where it cites” is the passage in the opinion; the holding is a summary of the whole case and may concern another point. Annotations are extracted automatically from the opinions in the Syfert caselaw corpus.

Citing cases by year
200420102016

One bar per year. Tallest: 1 case in 2004. These are opinions in the Syfert collection, which holds more of some courts’ recent opinions than their older ones, so a rise can reflect what the collection holds and not more litigation.

By court
Ga. Ct. App.1La. Ct. App.1D.R.I.1
By subsection
(d)1 case
Jones v. Centerpoint Energy Entex, 66 So. 3d 539 (La. Ct. App. 2011).“It was not disputed at trial that Center-point Energy’s applicable standard of care in disconnecting service to a customer is governed by 49 C.F.R. 192.727, which provides three methods of acceptable compliance: Whenever service to a customer is discontinued, one of the…”
(d)(1)1 case
Jones v. Centerpoint Energy Entex, 66 So. 3d 539 (La. Ct. App. 2011).
(d)(2)1 case
Jones v. Centerpoint Energy Entex, 66 So. 3d 539 (La. Ct. App. 2011).
(d)(3)1 case
Jones v. Centerpoint Energy Entex, 66 So. 3d 539 (La. Ct. App. 2011).
Enactment and amendments

Syfert holds no separate history line for this section. Where this code prints a source or history note, it appears with the text, usually at the end.

Versions

Edition shown: eCFR text as of Sept. 29, 2026. Syfert holds no earlier or later version of this section.

C.F.R. Home  |  Search C.F.R.  |  Search cases for this section  |  syfert.com